Your team needs a safe, controlled way to switch power sources when a utility feed goes down or a generator has to step in. You can move a load between two sources by hand with a Socomec MTS (manual transfer switch). It also has a clear off position for isolation. Read this guide to learn how a Socomec MTS works, which Socomec range is best for a given job, and what UAE building teams should look for before ordering or setting up one.
What Is a Socomec MTS and How Does It Work?
Socomec’s paperwork says that MTS means for Manual Transfer Switch, which is also written as MTSE for “Manual Transfer Switching Equipment.” A Socomec MTS is a multipole switch that moves a low-voltage load between two sources, like the power grid and a backup generator. It is handled by hand. Besides that, it keeps the circuit safe by isolating it.
Socomec also sets up the area for duty bypass. A SIRCOVER brochure says that a bypass version can make a UPS or a variable speed drive a safe system that can be changed out or maintained. This means that a Socomec MTS can be used for more than just switching between generators.
The I-0-II principle
A lot of manual switch models can work in three states: I (source 1), 0 (off), and II (source 2). To get to the other source, the operator moves the handle through 0. In a normal I-0-II setup, this means that the two sources are never linked together. There are also bypassed and overlapped versions on Socomec that behave in different ways. Always check the datasheet for your specific model to make sure the switching order is correct.
Manual versus automatic transfer
A manual switch needs a person on site. An automatic transfer switch (ATS) senses a source failure and transfers by itself. The two are closely related: Socomec states that a SIRCOVER can be motorised with ATyS modules, so a manual installation can be upgraded later.
Why a Socomec MTS Still Matters on UAE Sites
One of the safest grids in the world is in Dubai. In 2025, DEWA found that customers lost 0.82 minutes per year, compared to about 15 minutes for the top utilities in the European Union (DEWA world-class results). While that is good news, it does not mean that you don’t need transfer tools. Not planned outages happen very often, but planned work doesn’t.
On-load tests for generators still need to be done regularly. The ATS panels and UPS systems still need to be serviced. Switchboards still need to be turned off so that they can be inspected. A Socomec MTS gives your group a single, safe place to do all of these things.
Generator changeover
Commercial buildings, warehouses and industrial plants across Dubai, Abu Dhabi and Sharjah rely on standby generators. A Socomec MTS connects the generator through a defined switching sequence, which helps prevent back-feeding the utility network. For generator supply, testing or maintenance, see our generator services.
UPS and ATS maintenance bypass
In data centres and other critical facilities, a maintenance bypass lets engineers service equipment without dropping the load. Socomec’s ATyS Bypass brochure describes a test mode in which the ATS is isolated and can be tested and maintained without disturbing the load, while the manual changeover switch keeps the supply running. The same logic applies to UPS systems that need scheduled maintenance.
Heat, dust and humidity
You need to plan for extra stresses in UAE sites, like high temperatures in plant rooms, fine dust, and salty humidity near the coast. Find out what your real room temperature is by reading the manual’s derating instructions. Also, make sure the cage fits the area. Socomec has models with polyester coverings that are said to be resistant to chemical attack, dust, and corrosion from the air.
Socomec MTS Range at a Glance
Each Socomec manual transfer switch is put into a group based on its function and current rating. Socomec’s brochures and range listings were used to make the table below, which shows a summary of the main families. Always check the most recent official documents, like Socomec’s SIRCOVER page, to make sure that the ratings, poles, and accessories are correct.
| Family | Current range | Key traits | Typical use |
| SIRCO M | 25–125 A | Modular, 3 or 4 pole, DIN rail or back plate mounting | Small panels, sub-distribution |
| SIRCO VM1 | 63–125 A | Modular with visible break | Where visible isolation is preferred |
| SIRCOVER | 125–3,200 A | I-0-II, bypass, overlapped and enclosed versions | Main LV changeover, generator and plant |
| SIRCOVER ATS Bypass | 125–1,600 A | Manual bypass for an ATS | Maintaining an ATS without shutdown |
| SIRCOVER PV | 200–630 A | Designed for DC or photovoltaic circuits | Solar and DC applications |
For manual ranges above 125 A, SIRCOVER is the norm. For small jobs that need to be mounted on a panel, Socomec also makes COMO CS cam-based manual transfer switches, which start at 25 A.
The model family is only half of the decision in real life. You can change how the switch fits on your panel and how operators use it by adding things like door handles, extension shafts, auxiliary contacts, and terminal shrouds. You should list them along with the switch body and include the full part numbers in the bill of materials so that the site team gets a full, working set.
How to Choose the Right Socomec MTS
Selecting a Socomec MTS is not just a matter of matching amps. Work through these four checks with your design engineer.
Current rating and number of poles
Size the switch from the real load, not the nameplate. A load analysis study shows actual demand and future growth, so you avoid undersizing or paying for capacity you never use. Then decide between 3-pole and 4-pole. A 4-pole version switches the neutral. Whether you need that depends on the earthing system and the design, so confirm it with the responsible engineer.
Switching function
In order to switch between two sources normally, pick I-0-II. If you need to keep a UPS, ATS, or drive running without shutting it down, choose a workaround version. Overlapping versions and standard I-0-II versions work in different ways, so read Socomec’s documentation and your design needs carefully before choosing one.
Enclosure and environment
Match the protection level to the location. An air-conditioned electrical room needs less than a rooftop, a plant yard or a dusty workshop. Check the enclosure’s IP rating on the datasheet.
Future automation
If the site may later need automatic operation, ask whether your chosen model accepts motorisation. Confirm compatibility with Socomec before purchase, because this decision is far cheaper at design stage than after installation.
Installation and Safety Notes for UAE Sites
Transfer switches are very important parts of an electrical system, so mistakes cost a lot of money. A Socomec MTS should only be installed, used, or changed by qualified electrical professionals. What they have to do is follow the instructions from the maker and the rules set by the right authority, like DEWA in Dubai, ADDC in Abu Dhabi, or SEWA in Sharjah. Different projects have different needs, so make sure you know what they are.
A practical installation sequence:
- Download the official manual and datasheet for the exact part number from Socomec.
- Isolate all upstream sources, prove dead and apply lock-out and tag-out.
- Mount the switch as specified, using cables and lugs rated for the terminals.
- Tighten terminals to the torque stated in the manual. Never estimate it.
- Operate the handle with the load off and confirm the I-0-II sequence and any padlocking.
- Test on load with the generator, record the results and label each source clearly.
Some common problems that need to be fixed or commissioned are loose connections after thermal cycling, phase rotation that isn’t matched between the utility and generator, and door handles or shafts that aren’t lined up properly. Before you make the first transfer, check the phase order.
Socomec says that SIRCOVER doesn’t need any maintenance because its contacts clean themselves. Still, it’s a good idea to visually and thermally inspect the switch every so often in the dusty plant rooms of the UAE. Make this part of your preventative maintenance plan.
Socomec MTS vs ATS: When to Upgrade
A Socomec MTS is the right choice in some cases, and an automatic solution in others. Choose a manual switch when:
- The site is attended and a short interruption during manual changeover is acceptable.
- The main goal is safe isolation, generator connection or UPS and ATS bypass.
- Budget and simplicity matter more than automation.
Choose an automatic solution when:
- The site is unattended or needs fast recovery.
- Life-safety, data centre or process loads cannot wait for an operator.
- Remote control or monitoring is required.
Both are used in a lot of projects in the UAE. A common setup has an automatic transfer switch that works normally and a manual bypass that works around it. This way, the ATS can be tested or replaced while the load stays connected. This is why the choice between manual and automatic is rarely made separately. Most of the time, it comes down to how much maintenance, access, and strength the building needs.
These are the ATyS family from Socomec. They add a motor and a control device to the SIRCOVER design. Socomec also has STATYS static transfer switches from 16 to 1,600 A for IT loads that can’t be stopped. If you are comparing options, our team can review STS and ATS services alongside your wider data center infrastructure plan.
Work With DCPS ME on Your Socomec MTS Project
DCPS Middle East is a company in the UAE that adds together tools and offers solutions and services. For the data center market, we work on power, cooling, and connectivity. For the MEP market, we work on UPS, generators, VFDs, and batteries. We support, service, and integrate transfer switching equipment, such as Socomec MTSs in projects, as well as do the research, design, and maintenance that goes along with them.
In practice, that can include:
- Load and power system studies to confirm ratings and protection before you buy.
- Electrical design support so the transfer arrangement fits the single-line diagram.
- UPS, STS, ATS and generator services that connect to the same changeover scheme.
- 24×7 multi-vendor maintenance for data center infrastructure, under agreed service levels.
Controlling changeover and separation is easy and has been shown to work with a Socomec MTS. The best model, rating, and way to install it will still depend on the site, the loads, and the maintenance plan you have. Getting these choices right during the planning phase will save time and risk in the long run.